Temperature Split Range Control Output And Valve Open Relation
I have an ethoxylation process with temperature split range control question.
First
 I would like to introduce this process a little bit. The ethoxylation 
process is to produce non-ionic surfactants and PEG(polyethylene 
glycol). Fatty alcohols, or alkyl phenol are typically used as reactant 
with ethylene oxide. The reactor type is semi-batch liquid stirred 
reactor, equipped with a circulation loop to increase the reactor heat 
exchange capacity, and liquid EO is continuous dispersed into the 
gaseous one, followed by post-treatment operation such as catalyst 
removal to achieve the required quality of the product. The usual 
operation pressure in this process is 4~5 bara. Nitorgen will be purged 
to the reactor to assure the EO gases composition within the safety 
limits. Besides that, the reactor temperature is between 120 degree C to
 180 degree C and is kept constant by external regulation.
This
 PID(TIC-120) controller to keep the reactor temperature constant. The 
heat removal is made by water recirculation cooler and heat addition is 
made by water recirculation heater. TIC-120 measures the temperature at 
inlet of reactor heat exchanger by the temperature transmitter TE/TIT 
120 and acts on following valve,TV-120A, TV-120B and TV-120C. ( TIC -120
 output and TV-120A, B and C position is on the attached pdf) TIC-001 
measures the reactor bottom line temperature by TE/TIT-001 and act on 
set-point of 120 in cascade mode.
My question is the temperature control loop T-120.
Why do we have to set TIC-120 middle output as 50% instead of 70% to make valve action? 
My reason is that the slower valve should require longer time to react. 
It
 seems to for system take longer time to shut the TV-120A(steam valve 
close/open) so set TIC-120 output middle value as 70% seems more 
approaiate.
You will probably have a reason that you entered this question. It 
appears to me that it isn't just curiosity on the TIC-120 percentage 
setting for the valve TV-120A.
It appears to me that there are some mistyping errors in your data:
?    In the table TV-120A is closed at 50% of TIC-120, which conflicts with the graphic.
?    In the graphic it seems that the "TIC-120 output" and "Valve position" are mixed up.
If I understand your data correctly, following appears to happen starting with full heating:
?    At 0% TIC steam is full open on the steam HX. There is no cooling by the CW HX. The valve TV-120B is fully open.
?    If
 the temperature of the reactants at the discharge of the Reactor HX 
becomes too high, the TIC will give a higher value e.g. 20%. The steam 
supply will be reduced. Part of the water returning from the Reactor HX 
will be diverted to the CW HX.
?    At 50% TIC there will be no steam
 supply. Part of the water is diverted to the CW HX for cooling and the 
remainder bypasses the CW HX through the valve TV-120B.
?    In the range 50 ... 100 % TIC the quantity of cooling is increased to full CW HX cooling at 100% TIC. 
Whether
 a change in the closed position of valve(Globe Valves)TV-120A from 50% to 70% TIC 
would be beneficial, cannot be answered without detailed mass and heat 
balances.
You have an existing situation with HXs with a specific
 heat exchanging surface. An increase in TIC percentage for the closed 
position of TV-120A could be beneficial, if you have too abrupt cooling 
in the present situation, but note that flow quantities are changing.